Closed-loop current transformers
DESCRIPTION
In the case of bushing-type current transformers, the customer’s primary wire is pushed through the current transformer opening in the housing. The push-through opening depends on the size of the primary current.Wound primary-type current transformers have a primary winding and a secondary winding.
Both windings are applied on the closed toroidal core and are isolated from each other by insulation. This principle applies mainly where primary currents are small. Low-voltage current transformers for the proportional transformation of large currents to directly measurable smaller current values
Advantages
- Bolts or flat plug connection
- Bushing-type current transformers for direct conductor feedthrough
- Toroidal cores made of high-quality magnetic cores
- Frequency range 16 2/3 to 400 Hz optional
- High core output power and high-quality insulation (UL)
- circuits primaires et secondaires séparés électriquement
- Easy-to-assemble modular-type housing
- Variable connections, e.g. bolts, flat plugs, litz wires
- Wide range of housings with various push-through openings
Typical applications
Industry, Renewable energy sources, Railway engineering, Energy, automation and building technology
Type IE modular | 500 | 1000 | 2500 | ||
---|---|---|---|---|---|
IPN | Primary rated current | 500 | 1000 | 2500 | [A] |
ImaxPN | Max. Primary rated current | 600 | 1200 | 3000 | [A] |
IaN | Secondary current | 1000 | [mA] | ||
RB | Load resistance | 5 | 15 | 30 | [Ω] |
URB | Load voltage | 5 | 15 | 30 | [V] |
PSek | Power | 5 | 15 | 30 | [VA] |
KN | Transmission ratio | 500 | 1000 | 2500 | |
Fi | Measuring accuracy(50 Hz) | 0,5 | 0,5 | 0,5 | [%] |
f | Frequency | 50-400 | [Hz] | ||
TA | Ambient temperature | -25 bis +70 | [°C] | ||
Vp | Insulation test | 3 | [KVac] | ||
Connection | MS bolt / flat pin 6.3 x 0.8 | [mm²] | |||
Weight | 0,8 | 0,8 | 1,8 | [kg] | |
Standards | 61869-2 |
Type | I [mm] |
h1/h2 [mm] |
t1/t2 [mm] |
s1/s2 [mm] |
b1/b2 [mm] |
D [mm] |
D1xD2 [mm] |
f [mm] |
e [mm] |
x1/x2 [mm] |
IE modular 500 | 70 | 76/35 | 38/64 | 57/57 | 57/50 | 30,2 | 30,4×10,4 | 4,3 | 4,3 | 36/15 |
IE modular 1000 | 94 | 100/47 | 42/72 | 78/78 | 78/60 | 38,5 | 40,5×13,5 | 5,3 | 5,3 | 36/15 |
IE modular 2500 | 135 | 141/67,5 | 52/88 | 102/102 | 102/70 | 57,5 | 60,5×20,5 | 6,5 | 6,5 | 36/15 |
Download our extensive catalog and discover many other REO products.