Filter combination (single stage)
Description
By using a line reactor the upper harmonics are reduced and the starting current is limited. This increases the efficiency and discharges the leads.
Advantages
- Easy installation
- Small footprint
- Reduction of cable looms in control panels
- Attenuation of higher harmonics
- Low hum vacuum impregnated choke
- Reduced start-up current
- The choke is rated for a short-circuit voltage of 4%, at rated current, as standard
Typical applications
Interference suppression of frequency converters with IGBTs and reduction of harmonics (conforming to VDE 0160/EN 61800-3 class B)
- Conforming to: VDE 0565-3 / IEC 950 / UL 1283
- Test voltage: L-L 2100 V, DC 1s, L-PE 2700 V, DC 1s
- Overload: 1,5 x I 1 min/h
- Climatic category: DIN IEC 68 Part 1 25/085/21
Type | Nominal voltage [V] |
Nominal current [A] |
Leakage current[mA] | L [mH] | Cx [µF] | Cy [nF] | Rx [k] | Ry [k] |
CNW 304/80 | 3×400 | 80 | >35 | 1,2 | 1,5 | 600 | 560 | 560 |
CNW 304/120 | 3×400 | 120 | >35 | 0,5 | 3,5 | 870 | 560 | 560 |
CNW 304/150 | 3×400 | 150 | >35 | 0,6 | 3,5 | 870 | 560 | 560 |
Type | Connections | Dimensions [mm] | ||||||
Clamp | Earth | L 1 | L 2 | L 3 | B 1 | B 2 | H 1 | |
CNW 304/80 | 50 mm² | M10 | 330 | 315 | 290 | 190 | 120 | 216 |
CNW 304/120 | 50 mm² | M10 | 440 | 420 | 400 | 280 | 200 | 248 |
CNW 304/150 | 50 mm² | M10 | 440 | 420 | 400 | 280 | 200 | 248 |