Three-phase line reactor 2% Uk
Description
Compact & Efficient
The new series not only scores points for its faster delivery time, but also for its resource conservation and increased efficiency.
Power Noise Reduction – save up to 15% energy costs. A line reactor relieves the supply network by compensating the harmonics reactive power. The harmonics and commutation notches are reduced strongly. By using a line reactor the inverter electronics and DC-capacitors will be protected.
Starting currents and current peaks are reduced up to 30%. Line reactors help to comply with international power quality standards IEEE 519 or EN 61000-3-2.
Advantages
- Compact design
- Extended service life of electrical consumers
- Low-temperature rise
- Attenuation of current spikes up to 30%
- Reduction of input current up to 15%
- Low-noise
- Production possible according to UL insulation system E251513
Typical applications
Drive systems for motor drives: Mechanical engineering, Elevators / escalators, Pipes, Conveyor technology, Ventilation and air conditioning, Robotics, Automation technology, Power supplies and Wind turbines
Technical Data
- Rated voltage: U ≤ 3 x 500 V
- Short circuit: Uk 2% (400VAC/50Hz, INenn)
- Frequency: 50/60 Hz
- According to: EN 60289 / EN 61558
- Test voltage: LL 2500 V, DC 1min; L-PE 2500 V, DC 1min
- Insulation class: T40/F
- Protection rating: IP00
- Climatic category: DIN IEC 60068-1
- Overload: 1,5 x INenn 1 min / h
- Design: standing on foot angle
Type | Nominal voltage / nominal frequency UN [V] |
Nominal current IN [A] |
Inductance L [mH] |
Losses P [W |
Weight [kg |
Mass Cu [kg] |
Mass Al [kg] |
N CNW 903 /3 | 500 50 / 60 Hz |
3 | 9,800 | 16 | 1.0 | 0.2 | – |
N CNW 903 /6 | 500 50 / 60 Hz |
6 | 4,880 | 25 | 2.0 | 0.3 | – |
N CNW 903 /8 | 500 50 / 60 Hz |
8 | 3,680 | 35 | 2.0 | 0.3 | – |
N CNW 903 /10 | 500 50 / 60 Hz |
10 | 2,930 | 36 | 3.0 | 0.4 | – |
N CNW 903 /12 | 500 50 / 60 Hz |
12 | 2,450 | 38 | 3.0 | 0.45 | – |
N CNW 903 /16 | 500 50 / 60 Hz |
16 | 1,830 | 48 | 4.0 | 0.7 | – |
N CNW 903 /25 | 500 50 / 60 Hz |
25 | 1,170 | 63 | 5.2 | 0.8 | – |
N CNW 903 /36 | 500 50 / 60 Hz |
36 | 0,810 | 67 | 7.0 | 1.9 | – |
N CNW 903 /50 | 500 50 / 60 Hz |
50 | 0,590 | 112 | 9.0 | 1.2 | – |
N CNW 903 /70 | 500 50 / 60 Hz |
70 | 0,420 | 180 | 11 | 2.1 | – |
N CNW 903 /90 | 500 50 / 60 Hz |
90 | 0,330 | 144 | 17 | 2.5 | – |
N CNW 903 /110 | 500 50 / 60 Hz |
110 | 0,270 | 179 | 18 | 1.8 | – |
N CNW 903 /125 | 500 50 / 60 Hz |
125 | 0,235 | 220 | 17 | 2.6 | – |
N CNW 903 /160 | 500 50 / 60 Hz |
160 | 0,180 | 145 | 22 | 5.0 | – |
N CNW 903 /200 | 500 50 / 60 Hz |
200 | 0,147 | 187 | 26 | 1.3 | 3.8 |
N CNW 903 /250 | 500 50 / 60 Hz |
250 | 0,118 | 254 | 35 | 1.3 | 3.0 |
N CNW 903 /300 | 500 50 / 60 Hz |
300 | 0,098 | 250 | 37 | 1.3 | 4.7 |
N CNW 903 /350 | 500 50 / 60 Hz |
350 | 0,084 | 267 | 45 | 2.6 | 5.0 |
N CNW 903 /400 | 500 50 / 60 Hz |
400 | 0,074 | 365 | 52 | 2.6 | 5.2 |
N CNW 903 /500 | 500 50 / 60 Hz |
500 | 0,059 | 423 | 58 | 2.9 | 7.8 |
N CNW 903 /600 | 500 50 / 60 Hz |
600 | 0,049 | 450 | 71 | 5.0 | 6.9 |
N CNW 903 /700 | 500 50 / 60 Hz |
700 | 0,042 | 493 | 88 | 5.0 | 9.2 |
N CNW 903 /800 | 500 50 / 60 Hz |
800 | 0,037 | 545 | 96 | 5.1 | 8.3 |
N CNW 903 /900 | 500 50 / 60 Hz |
900 | 0,033 | 655 | 108 | 12.5 | 10.1 |
N CNW 903 /1000 | 500 50 / 60 Hz |
1000 | 0,029 | 775 | 108 | 12.5 | 10.1 |
N CNW 903 /1200 | 500 50 / 60 Hz |
1200 | 0,024 | 1009 | 133 | 13.9 | 12.4 |
Type | Lenght L1 (mm) | Lenght L2 (mm) | Broad B1 (mm) | Broad B2 (mm) | High max. H1 (mm) | Mounting N1 (mm) | Attachment N2 (mm) | Attachment D1 (mm x mm) | Terminal/ Cable lug [mm²] |
Angle [mm x mm] |
Connection A1 (mm) | Connetion D2 (mm) | PE |
N CNW 903 /3 | 65 | 78 | 50 | 60 | 95 | 50 | 38 | 5 x 8 | 2.5 | M4 | |||
N CNW 903 /6 | 80 | 96 | 55 | 65 | 110 | 56 | 43 | 5 x 8 | 2.5 | M4 | |||
N CNW 903 /8 | 125 | 120 | 61 | 66 | 130 | 100 | 45 | 5 x 8 | 2.5 | M4 | |||
N CNW 903 /10 | 125 | 120 | 71 | 76 | 130 | 100 | 55 | 5 x 8 | 2.5 | M4 | |||
N CNW 905 /12 | 125 | 120 | 71 | 76 | 130 | 100 | 55 | 5 x 8 | 2.5 | M4 | |||
N CNW 903 /16 | 155 | 150 | 76 | 76 | 155 | 130 | 54 | 8 x 12 | 2.5 | M4 | |||
N CNW 903 /25 | 155 | 150 | 91 | 101 | 170 | 130 | 69 | 8 x 12 | 10 | M4 | |||
N CNW 903/36 | 190 | 180 | 81 | 91 | 195 | 170 | 57 | 8 x 12 | 10 | M6 | |||
N CNW 903 /50 | 190 | 180 | 101 | 111 | 195 | 170 | 77 | 8 x 12 | 10 | M6 | |||
N CNW 903 /70 | 230 | 136 | 200 | 176 | 73 | 9 x 13 | 16 (M8) | 45 | M8 | ||||
N CNW 903 /90 | 230 | 150 | 200 | 176 | 95 | 9 x 13 | 16 (M8) | 45 | M8 | ||||
N CNW 905 /110 | 240 | 150 | 210 | 185 | 97 | 10 x 18 | 16 (M8) | 45 | M8 | ||||
N CNW 905 /125 | 240 | 150 | 210 | 185 | 95 | 10 x 18 | 45 | M8 | |||||
N CNW 903 /160 | 240 | 175 | 210 | 185 | 103 | 10 x 18 | 35 (M10) | 55 | M8 | ||||
N CNW 903 /200 | 300 | 148 | 270 | 224 | 95 | 10 x 18 | 30 x 4 | 39 | 11 | M12 | |||
N CNW 903 /250 | 300 | 184 | 270 | 224 | 125 | 10 x 18 | 30 x 4 | 39 | 11 | M12 | |||
N CNW 903 /300 | 300 | 190 | 270 | 224 | 125 | 10 x 18 | 30 x 4 | 39 | 11 | M12 | |||
N CNW 903 /350 | 340 | 192 | 305 | 248 | 130 | 10 x 18 | 40 x 5 | 49 | 13 | M12 | |||
N CNW 903 /400 | 360 | 195 | 315 | 264 | 142 | 10 x 18 | 40 x 5 | 49 | 13 | M12 | |||
N CNW 903 /500 | 360 | 200 | 345 | 264 | 142 | 10 x 18 | 40 x 5 | 49 | 13 | M12 | |||
N CNW 903 /600 | 360 | 232 | 345 | 264 | 167 | 10 x 18 | 40 x 5 | 58 | 13 | M12 | |||
N CNW 903 /700 | 420 | 240 | 370 | 316 | 174 | 13 x 20 | 40 x 5 | 58 | 13 | M12 | |||
N CNW 903 /800 | 420 | 275 | 380 | 316 | 184 | 13 x 20 | 60 x 5 | 68 | 2 x 13 | M12 | |||
N CNW 903 /900 | 480 | 263 | 465 | 356 | 158 | 13 x 20 | 60 x 10 | 78 | 2 x 13 | M12 | |||
N CNW 903 /1000 | 480 | 263 | 465 | 356 | 158 | 13 x 20 | 60 x 10 | 78 | 2 x 13 | M12 | |||
N CNW 903 /1200 | 480 | 265 | 500 | 356 | 168 | 13 x 20 | 60 x 10 | 78 | 2 x 13 | M12 |