Complete catalogue

Download our extensive catalogue and discover many more products from REO.

Active Current Transformer Series WKO

Closed-loop current transformers

Description

Closed-loop current transformers

The WKO current sensors work according to the proven compensation principle and are suitable for measuring direct, alternating and mixed currents. The primary current flow generates a magnetic flux, which is compensated by an internal secondary coil.
The current evaluation is realized with an electronic circuit and a Hall sensor. The secondary compensation current is an exact reflection of the primary current to be measured.

Unique Selling Point

  • Measurement of direct, alternating and mixed currents
  • Very high precision and short response time
  • Broad frequency spectrum and low-temperature drift
  • Very good linearity and overcurrent resistance
  • No additional losses in the measuring circuit (DC to 150 kHz)
  • Current output for lengthy transmission lines
  • High-quality UL-listed insulating materials (e.g. UL94-V0)

UNIQUE SELLING POINT

  • Robust housing designs (for horizontal/vertical mounting)
  • Variable connections, e.g. clamps, plugs, flat-cable plugs or cables
  • Wide range of housings with various push-through openings
  • Push-through openings

Typical applications

Industry, Renewable energy sources, Railway engineering, Energy, automation and building technology
Type WKO 25 WKO 50 WKO 100 WKO 300 WKO 500 WKO 1000
Primary RMS nominal current
IPN [A]
25 50 100 300 500 1000
Measuring range
IP [A]
0…±35 0…±70 0…±150 0…±500 0…±1000 0…±1500
Supply
UC [V]
±12 …15 ±12 …15 ±12 …15 ±12 …15 ±12 …24 ±12 …24
Measuring accuracy
XG@Ipn
[-20…70°C]
from IPN [%]
> ±0,9 > ±1 > ±1 > ±1 > ±1 > ±1
Translation
KN
1000 1000 1000 2000 5000 5000
Secondary RMS
Nominal current ISN [mA]
25 50 100 150 100 200
Secondary winding
Resistive sand
RS@70°C [Ω]
16 43 24 30 72 48
Idle current
[mA]
36+IS 11+IS 36+IS 36+IS 36+IS 24+IS
Type WKO 25 WKO 50 WKO 100 WKO 300 WKO 500 WKO 1000
Linearity error
e [%]
< ±0,1 < ±0,1 < ±0,1 < ±0,1 < ±0,1 < ±0,1
Offset error@25°CIO [mA] > 0,3 > 0,3 > 0,4 > 0,2 > 0,2 > 0,3
Offset Drift-25°C…+70°CIOT [mA] > 0,5 > 0,5 > 1 > 0,5 > 0,5 > 0,5
Response time
tra[μs]
> 0,5 > 0,5 > 0,5 > 0,5 > 0,5 > 0,5
Response time
10%-90%
ta [μs]
> 1 > 1 > 1 > 1 > 1 > 1
dl/dt
ta [A/μs]
> 50 > 50 > 100 > 100 > 100 > 100
Bandwidth
-1 dB [kHz]
DC…150 DC…200 DC…100 DC…100 DC…100 DC…100
Type WKO 25 WKO 50 WKO 100 WKO 300 WKO 500 WKO 1000
Creepage distance
dCp [mm]
4 8 10 10 10 15
Air section
dCi[mm]
3 7 9 9 9 12
Leakage current resistance
[CTI]
600 600 600 600 600 600
AC insulation test
50/60Hz 1min
Ud [kV]
3,8 3,8 3,8 3,8 6 6
Pulse voltage test
1,2/50μs
Ui[kV]
6 6 6 6 12,5 14,5
Mass
[kg]
0,08 0,022 0,125 0,125 0,240 0,450
Type Pin connection/
4-pin
h
[mm]
b
[mm]
b1/b2
[mm]
t
[mm]
DL
[mm]
p/s
[mm]
a/a1
[mm]
c1/c2
[mm]
f
[mm]
e
[mm]
l
[mm]
WKO 25 A; -U; +U 39 39 26 10 2 x 10/6,5 25/6,5 M3 6,0 x 4,0 9
WKO 50 A; -U; +U Please find in the drawing
WKO 100 A; -U; +U 55 55/68 26 20,2 45/45 13,0/– 4,3 6,0×4,0 12
WKO 300 A; -U; +U 55 55/68 26 20,2 45/45 13,0/– 4,3 6,0×4,0 12
WKO 500 A; -U; +U 70 70/89 33 31,0 57/57 15,2/– 4,3 6,0×4,3 12
WKO 1000 A; -U; +U 95 94/110 44 40,0 78/78 18,0/– 5,3 8,0×5,3 12