Complete catalogue

Download our extensive catalogue and discover many more products from REO.

du/dt Choke N CNW 806

Three-phase dv/dt filter

DESCRIPTION

NEW SERIES! The new series not only scores points for its faster delivery time, but also for its resource conservation and increased efficiency. Reduce voltage rise to < 500V / µs – protect electrical loads and insulation cost-effectively. A simple and cost-effective method to reduce the voltage rise rate is to use a du/dt choke or filter. It dampens the voltage rise to tolerable values and prevents overvoltages on long supply lines. Losses and heating are minimized, and the leakage current is reduced. By limiting the voltage steepness, the motor insulation is protected, thus extending its service life. EMC interference in the radiation range from 1 MHz to 30 MHz is also reduced.

ADVANTAGES

  • Protection for electrical consumers
  • Limitation of voltage rise to < 500V / µs
  • Extended service life of electrical consumers
  • Low leakage currents on the motor
  • Reduced losses
  • Easy construction
  • Compact design
  • Production possible according to UL insulation system E251513

TYPICAL APPLICATIONS

Drive systems for motor drives, Mechanical engineering, Elevators / escalators, Pipes, Conveyor technology, Ventilation and air conditioning, Robotics, Automation technology, Power supplies, Wind turbines

Technical Data

  • Rated voltage: U ≤ 3 x 500 V
  • Reduction of voltage rise du/dt to < 500V/µs
  • Field frequency: 0 – 60 Hz Drive
  • Switching frequency of the inverter: up to 150 A >4kHz, from 150 A >1.5kHz
  • According to: EN 60289 / EN 61558
  • Test voltage: L-L 2500 V, AC/50Hz 60s; L-PE 2500 V, AC/50Hz 60s
  • Insulation class: T40/F
  • Protection rating: IP00
  • Climatic category: DIN IEC 60068-1
  • Overload: 1,5 x INenn 1 min / h
  • Ambient temperature: 40 °C
  • Design: standing on foot angle
Type Nominal voltage
U [V]
Nominal current
I [A]
Inductance
L [mH]
Resistance
R [mΩ]
Losses
P [W]
UK at
400 V,
50 Hz
[%]
UK at
230 V,
50 Hz
[%]
UK at
480 V,
60 Hz
[%]
UK at
500 V,
50 Hz
[%]
Mass
[kg]
[kg]
Weight
Cu
[kg]
Weight
Al
[kg]
N CNW 806 / 4 500
50 / 60 Hz
4 1,500 92,7 10 0,8 1,4 0,8 0,7 1,0 0,12
N CNW 806 / 10 500
50 / 60 Hz
10 0,600 26,4 20 0,8 1,4 0,8 0,7 2,0 0,15
N CNW 806 / 18 500
50 / 60 Hz
18 0,330 12,0 20 0,8 1,4 0,8 0,6 2,0 0,21
N CNW 806 / 24 500
50 / 60 Hz
24 0,245 9,1 30 0,8 1,4 0,8 0,6 2,5 0,24
N CNW 806 / 37 500
50 / 60 Hz
37 0,160 4,8 30 0,8 1,4 0,8 0,6 3,0 0,57
N CNW 806 / 48 500
50 / 60 Hz
48 0,123 2,7 40 0,8 1,4 0,8 0,6 3,0 0,45
N CNW 806 / 65 500
50 / 60 Hz
65 0,090 2,0 50 0,8 1,4 0,8 0,6 4,0 0,57
N CNW 806 / 90 500
50 / 60 Hz
90 0,065 1,5 60 0,8 1,4 0,8 0,6 5,0 0,72
N CNW 806 / 120 500
50 / 60 Hz
120 0,050 1,1 80 0,8 1,4 0,8 0,7 7,0 1,44
N CNW 806 / 150 500
50 / 60 Hz
150 0,039 0,5 60 0,8 1,4 0,8 0,6 8,0 1,65
N CNW 806 / 180 500
50 / 60 Hz
180 0,033 0,5 80 0,8 1,4 0,8 0,6 9,0 1,35
N CNW 806 / 200 500
50 / 60 Hz
200 0,029 0,5 100 0,8 1,4 0,8 0,6 9,0 1,50
N CNW 806 / 250 500
50 / 60 Hz
250 0,024 0,22 120 0,8 1,4 0,8 0,7 15,0 1,10 1,50
N CNW 806 / 300 500
50 / 60 Hz
300 0,020 0,15 140 0,8 1,4 0,8 0,7 16,0 1,10 2,55
N CNW 806 / 350 500
50 / 60 Hz
350 0,017 0,13 140 0,8 1,4 0,8 0,6 21,0 6,5
N CNW 806 / 400 500
50 / 60 Hz
400 0,015 0,10 150 0,8 1,4 0,8 0,7 24,0 2,2 2,25
N CNW 806 / 500 500
50 / 60 Hz
500 0,012 0,10 200 0,8 1,4 0,8 0,7 27,0 2,60 3,30
N CNW 806 / 600 500
50 / 60 Hz
600 0,010 0,08 250 0,8 1,4 0,8 0,7 32,0 4,40 2,55
N CNW 806 / 700 500
50 / 60 Hz
700 0,008 0,07 260 0,8 1,3 0,8 0,6 35,0 4,90 3,00
N CNW 806 / 800 500
50 / 60 Hz
800 0,007 0,06 280 0,8 1,3 0,8 0,6 36,0 5,20 3,90
N CNW 806 /900 500
50 / 60 Hz
900 0,0065 0,05 290 0,8 1,4 0,8 0,6 55,0 10,8 5,55
N CNW 806 / 1000 500
50 / 60 Hz
1000 0,006 0,05 360 0,8 1,4 0,8 0,7 56,0 10,8 5,85
N CNW 806 / 1200 500
50 / 60 Hz
1200 0,005 0,05 480 0,8 1,4 0,8 0,7 56,0 10,8 6,00
Type Length Width High max. Mounting Clamps/Cross
section [mm²]
Connection
L1 [mm] L2 [mm] B1 [mm] B2 [mm] H1 [mm] N1 [mm] N2 [mm] D1 [mm x mm] Angle [mm x mm] A1 [mm] D2 [mm] PE Ø [mm]
N CNW 806 / 4 65 78 50 60 95 50 38 5 x 8 2,5 M4
N CNW 806 / 10 80 96 45 55 110 65 34 5 x 8 2,5 M4
N CNW 806 / 18 80 96 5 65 110 65 43 5 x 8 2,5 M4
N CNW 806 / 24 125 120 61 76 145 100 45 5 x 8 10 M4
N CNW 806 / 37 125 90 105 100 45 5 x 8 10 (M6) 40 M6
N CNW 806 / 48 125 100 105 100 55 5 x 8 10 (M6) 40 M6
N CNW 806 / 65 155 110 130 130 54 8 x 12 16 (M8) 40 M6
N CNW 806 / 90 155 120 130 130 69 8 x 12 16 (M8) 40 M6
N CNW 806 / 120 190 115 160 170 57 8 x 12 25 (M8) 45 M8
N CNW 806 / 150 190 130 160 170 67 8 x 12 25 (M10) 45 M10
N CNW 806 / 180 190 140 160 170 77 8 x 12 25 (M10) 45 M10
N CNW 806 / 200 190 140 160 170 77 8 x 12 25 (M10) 45 M10
N CNW 806 / 250 240 145 210 185 84 10 x 18 30 x 4 45 11 M12
N CNW 806 / 300 240 140 210 185 84 10 x 18 30 x 4 45 11 M12
N CNW 806 / 350 240 155 210 185 84 10 x 18 40 x 5 50 13 M12
N CNW 806 / 400 300 150 265 224 95 10 x 18 40 x 5 50 13 M12
N CNW 806 / 500 300 160 295 224 95 10 x 18 40 x 5 50 13 M12
N CNW 806 / 600 300 177 295 224 105 10 x 18 40 x 8 60 13 M12
N CNW 806 / 700 300 177 325 224 105 10 x 18 40 x 8 60 13 M12
N CNW 806 / 800 300 195 325 224 105 10 x 18 60 x 5 70 2 x 13 M12
N CNW 806 /900 420 207 390 316 124 10 x 18 60 x 10 80 2 x 13 M12
N CNW 806 / 1000 420 217 390 316 124 13 x 20 60 x 10 80 2 x 13 M12
N CNW 806 / 1200 420 217 390 316 124 13 x 20 60 x 10 80 2 x 13 M12

Download our extensive catalog and discover many other REO products.

Download Datenblatt

Suitable for this product