Complete catalogue

Download our extensive catalogue and discover many more products from REO.

Passive Current Transformer Series Ie (Stranded Wire / Terminal)

Bushing-type current transformers

Description

In the case of bushing-type current transformers, the customer’s primary wire is pushed through the current transformer opening in the housing. The push-through opening depends on the size of the primary current. Wound primary type current transformers have a primary winding and a secondary winding. Both windings are applied on the closed toroidal core and are isolated from each other by insulation. This principle applies mainly where primary currents are small.

Advantages

  • Litz wires or terminals according to UL 94 V0
  • Bushing-type current transformers
  • Wound primary type current transformer, version for small currents
  • Toroidal cores made of high-quality silicon-iron
  • Measurement in the low-frequency range 16 2/3 to -400Hz
  • High core output power and high-quality insulation (UL)
  • circuits primaires et secondaires séparés électriquement
  • des formes faciles à monter
  • Wide range of housings with various push-through openings

UNIQUE SELLING POINT

  • des formes faciles à monter
  • Variable connections, e.g. clamps, plugs, flat-cable plugs, flexible stranded wire or print mounting
  • Wide range of housings with various push-through openings
  • Push-through openings
  • Very long useful lifetime

Typical applications

Industry, Renewable energy sources, Railway engineering, Energy, automation and building technology
Type 50 100 300 500 1000 2000 3000
Primary rated current [A] IPN 50 100 300 500 1000 2000 3000
Max. Primary rated current [A] ImaxPN 60 120 360 600 1200 2400 3600
Secondary current [mA] IaN 1000 1000 1000 1000 1000 1000 1000
Power [VA] Psek 0,5 1,0 2,5 10 15 25 25
Ratio KN 50 100 300 500 1000 2000 3000
Load resistance [Ω] RB 0,5 1,0 2,5 10 15 25 25
Load voltage [V] URB 0,5 1,0 2,5 10 15 25 25
Measuring accuracy 50 Hz [%] FU 1,0 1,0 1,0 1,0 1,0 1,0 1,0
Ambient temperature [°C] TA -25 to + 70 -25 to + 70 -25 to + 70 -25 to + 70 -25 to + 70 -25 to + 70 -25 to + 70
Frequency range [Hz] f 50 to 400 50 to 400 50 to 400 50 to 400 50 to 400 50 to 400 50 to 400
Insulation test voltage [kVac] VP 3 3 3 3 3 3 3

Download our extensive catalog and discover many other REO products.